After entering the PIN, the display can be used to start a teaching procedure
for the code sequences. The monitor stops immediately after entering the
PIN. After teaching, the monitor starts after a prompt and acknowledgement
on the display.
Action
Configure and load into Safety
Monitor
Stopping
Releasing
Starting
Teaching code sequences
Changing the password
Changing the PIN
Legend: "
Code sequences for releasing a configuration do not necessarily have to have
been successfully learned. It is also possible to release without code sequences,
which must then be learned at a later time. An AS-i Safety Monitor does not go
into the protecting operating mode without learned code sequences.
Teaching the code sequences is simple to perform:
Using the ESC/Service key (See section <Replacing a defective safety-con-
figured AS-i slave>)
or
Using the display (See section <TEACH CODES>).
8.5.2

Function of the ESC/Service key

In traditional (classical) display mode, the ESC/Service key takes on two kinds of
functions:
Briefly pressing the ESC/Service key unlocks the Safety Monitor when red is
flashing
A longer press (3s) starts the teach procedure for a slave.
Information!
For additional information see section <Replacing a defective safety-configured AS-i
slave>.
50
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91
AS-i 3.0 EtherNet/IP Gateway with integrated Safety Monitor
ASIMON Software
" = possible; "–" = not possible
Function and startup of the Safety Monitor
On AS-i Safety Monitor
(only from chip card)
(only from chip card)
© Pepperl+Fuchs, Printed in Germany
Internet http://www.pepperl-fuchs.com