Data Not Identical; Operating The Chip Card From The Menu; Working With Multiple Memory Banks - Pepperl+Fuchs VBG-EN-K30-DMD-S16 Manual

Ethernet/ip gateway with integrated safety monitor
Table of Contents

Advertisement

8.7.2.5

Data not identical

If the active bank on the memory card and in the device are not empty at start and
the data are not identical, the following message is displayed:
The safety unit will not operate in this case. You must either clear the device or
the active bank via menu.
8.7.2.6

Operating the chip card from the menu

The data on the chip card can, as described in section <SAFE CHIPCARD>, be
exchanged between the Monitor and the chip card. Note however the following:
In order to store a configuration on the chip card as a master configuration (i.e.
without code sequences), proceed as follows:
Write the released configuration into the Monitor without code sequences.
Copy the configuration into a memory bank using the menu.
For additional information, see section <CARD –>MONITOR (copy card data to
the Monitor)>.
To convert a master configuration on the memory card to a Complete Configura-
tion, this configuration must be overwritten by a Complete Configuration.
This is done as follows:
Copy the card data to the Monitor.
Teach the code sequences
Write the data from the Monitor to the card.
8.7.3

Working with multiple memory banks

The chip card has four memory banks, each of which may contain a configuration
(Complete or Master configuration). One of the banks is the active bank.
The AS-i 3.0 EtherNet/IP Gateway with integrated Safety Monitor always inde-
pendently utilizes the active bank. Menu commands can however be used to
copy the other memory banks to the AS-i Safety Monitor.
The corresponding memory bank thereby becomes the active bank.
If configurations from another memory bank are copied, a few safety rules need
to be followed:
Subject to reasonable modifications due to technical advances.
Pepperl+Fuchs Group · Tel.: Germany (6 21) 7 76-0 · USA (3 30) 4 25 35 55 · Singapore 7 79 90 91
Function and startup of the Safety Monitor
ERROR.
CHIPCARD AND
SAFETY DATA
DIFFERENT.
DELETE CHIPCARD
OR SAFETY DATA
AS-Interface
© Pepperl+Fuchs, Printed in Germany
Internet http://www.pepperl-fuchs.com