Dil Switch Settings - Festo CPX-AB Series Electronic Manual

Cpx terminal/analogue i/o modules, sub-bases type
Hide thumbs Also See for CPX-AB Series:
Table of Contents

Advertisement

2. Analogue input module CPX−2AE−U−I

2.3.1 DIL switch settings

1
DIL switch 0:
Signal range of
analogue input 0
2
DIL switch 1:
Signal range of
analogue input 1
Fig. 2/1: DIL switches in the electronic module
(further information on 1 and 2 see following pages)
2−6
2 DIL switches are available for configuring the analogue
input modules. These are located on the top of the electronic
module.
2
AI
ON
1
2
ON
1
2
Proceed as follows:
1. Switch off the power supply.
2. Remove if necessary the fitted sub−base (see Fitting"
section 1.3).
3. Set the DIL switch elements in accordance with the
instructions on the following pages.
4. Refit if necessary the sub−base (see Fitting" section 1.3,
tightening torque 0.9 ... 1.1 Nm).