Mounting; Settings Of The Dil Switches On The Bus Node; Removing And Attaching The Dil Switch Cover - Festo CPX Series Manual

Bus node fieldbus protocol cc-link
Hide thumbs Also See for CPX Series:
Table of Contents

Advertisement

2
Installation as function module F24
2.3.2

Mounting

Mount the bus node as follows:
1. Check the seal and the sealing surface.
2. Place the bus node in the interlinking block. Make sure that the corresponding slots with the con-
tacting terminals on the bottom of the bus node are above the contact rails.
3. Push the bus node carefully and without tilting as far as possible into the interlinking block.
4. Only tighten the screws by hand. Set the screws so that the self-cutting threads can be used.
5. Tighten the screws with a TORX screwdriver size T10 with 0.9 ... 1.1 Nm torque.
2.4

Settings of the DIL switches on the bus node

Note
This section describes how the DIL switch is set in the configuration of the bus node, as
a function module F24 (support of CC-Link version 2.0).
In order to set the bus node, you must first remove the cover for the DIL switches.
Caution
The CPX bus node for CC-Link contains electrostatically sensitive devices.
• Therefore, do not touch any components.
• Observe the handling specifications for electrostatically sensitive devices.
They will help you avoid damage to the electronics.
2.4.1

Removing and attaching the DIL switch cover

You need a TORX screwdriver size T10 to remove or attach the DIL switch cover.
Note
Observe the following instructions when removing or attaching the DIL switch cover:
• Disconnect the power supply before removing the DIL switch cover.
• Make sure that the seal is seated correctly when fitting the cover.
• Tighten the two fastening screws at first by hand and then with max. 0.4 Nm.
Festo – P.BE-CPX-FB23-24-EN – 1305a – English
13