2. Analogue input module CPX−2AE−U−I
1
Physical measuring
variables
2
Digital signals after
A−D conversion
(resolution: 12 bits)
3
Available digital
signals after scaling
by the scaling end
values
Fig. 2/5: Example scaling data format VZ + 15 bits linear scaled"
1
Digital input signal
after scaling
2
Limits
3
Less than or
exceeding the limits
Fig. 2/6: Limit monitoring with data format VZ + 15 bits linear scaled"
Festo P.BE−CPX−AX−EN en 0503b
Scaling end values with data format VZ + 15 bits
linear scaled"
The following diagram shows an example of the data format
VZ + 15 bits linear scaled" with the scaling end values:
Lower limit = 0
Upper limit = 6000
The example shows a sensor which converts the range of the
physical measuring variables from 0...6 bar linear into the
analogue signals 0...10 V or 0...20 mA.
1
0
2
0
3
0
The scaling end values in this data format are identical with
the limits for less than or exceeding the rated range:
2
1
0
3
6 bar
4095
6000
2
6.000
2−29