5. Analogue output module CPX−2AA−U−I
5.4.5 Channel−specific module parameter Limits
1)
Data format
VZ + 15 bits
linear scaled
VZ + 12 bits
right−justified
VZ + 15 bits
left−justified
VZ + 12 bits
left−justified
1)
(VZ = sign)
As the analogue outputs can only output positive signals and as there is no scaling on the data
range with the Fixed value" data formats VZ + 12 bits right−justified", VZ + 15 bits left−justified"
and VZ + 12 bits left−justified", the sign bit with these formats is always 0.
2)
The lower limit/scaling end value must always be less than the upper limit/scaling end value.
Tab. 5/20: Limits or scaling end values of the analogue output modules
Festo P.BE−CPX−AX−EN en 0503b
You can determine limits with the channel−specific para
meters Lower limit" and Upper limit". The meaning of the
limit parameters depends on the parametrized data format of
the module.
With data format VZ + 15 bits linear scaled", the limits have
the function of defining the scaling end values of the data
range. This results in an additional scaling of the analogue
values.
If the output data lie outside this data range, a diagnostic
message can be generated with appropriate parametrizing.
With other data formats the data range is already defined by
the scaling end values. In this case, the limits permit data
monitoring even within the data range.
Data range
−30000...+30000
0...4095
0...32760
0...32760
Limits/scaling end values
Lower scaling end value:
−30000...+29999
Lower limit:
0...4094
Lower limit:
0...32759
Lower limit:
0...32752
2)
Upper scaling end value:
−29999...+30000
Upper limit:
1...4095
Upper limit:
1...32760
Upper limit:
1...32760