Advertisement

5. Analogue output module CPX−2AA−U−I
Fault number
3
9
10
15
1)
The module displays the relevant fault depending on the parametrizing. The analogue output
signals, however, will be processed further.
2)
Processing of the analogue output signals will be stopped.
Tab. 5/22: Fault messages of the output modules part 2
5−34
Description
Wire fracture/idling
1)
Current output
Only with current outputs with signal
range 0/ 4...20 mA:
The wire−fracture monitoring is only
effective if more than approx. 1 mA
output current is output.
(See parameter Monitoring channel x
monitoring wire fracture/idling")
Less than the rated range
Lower limit exceeded.
(See parameter Lower limit channel x
low byte/high byte" or Monitoring
channel x monitoring below rated
range")
Rated range exceeded
Upper limit exceeded.
(See parameter Upper limit channel x
low byte/high byte" or Monitoring
channel x monitoring rated range
exceeded")
Module/channel failed
General fault, module faulty.
Fault treatment
Check and, if necessary, replace the
·
cable and connected actuators.
1)
Check signal range of output.
·
Check parametrized limit.
·
If necessary, deactivate monitoring.
·
1)
Check signal range of output.
·
Check parametrized limit.
·
If necessary, deactivate monitoring.
·
2)
Power off/on necessary
·
If this fault occurs again: check
·
and, if necessary, replace the
analogue output module.
Evaluation of the analogue output
signals has stopped.
Festo P.BE−CPX−AX−EN en 0503b