2. Analogue input module CPX−2AE−U−I
Channel parameters: Filter measured value channel x
4828 + m * 64 + 9
Function no.
Description
For the individual channels of the analogue input modules, the filter for
measured values can be set independently of each other.
Bit
Bit 0, 1:
Bit 2, 3:
Bit 4, 5:
Bit 6, 7:
Values
Channel 0
Bit 1 Bit 0
0
0
1
1
Remark
Faults can be suppressed with the Filter measured value (see section 2.5.1).
The reserved bits 2, 3 and 6, 7 must always be 0. If these bits are set to 1"
during parametrizing, the parametrizing carried out is invalid and therefore not
effective.
If the module parameter Monitoring parametrizing faults" as well as the
relevant channel parameter Monitoring parametrizing faults" is set to active",
the relevant fault will be displayed.
Tab. 2/15: Filter measured value channel x
Festo P.BE−CPX−AX−EN en 0503b
filter measured value channel 0
reserved (= 0)
filter measured value channel 1
reserved (= 0)
Channel 1
Bit 5 Bit 4
0
0
0
No filter measured value (presetting)
1
0
1
Filter measured value over 2 values
0
1
0
Filter measured value over 4 values
1
1
1
Filter measured value over 8 values
m = module number (0 ... 47)
2−23