Festo CPX-AB Series Electronic Manual page 144

Cpx terminal/analogue i/o modules, sub-bases type
Hide thumbs Also See for CPX-AB Series:
Table of Contents

Advertisement

4. Analogue input module CPX−4AE−T
Channel parameters: Measured value smoothing channel x
Function no.
4828 + m * 64 + 9 (channel 0 ... 3)
Description
Sets whether or not the measured values of the individual channels are to be
smoothed. The parameter can be set for the individual channels independently of
each other.
Bit
Bit 0/1:
Bit 2/3:
Bit 4/5:
Bit 6/7:
Values
Channel 3
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
0
1
1
Remark
Interference can be suppressed with the measured value smoothing.
Tab. 4/12: Measured value smoothing channel x
Channel parameters: Sensor connection designs channel x
Function no.
4828 + m * 64 + 10
Description
Set the connection design of the temperature sensor for the channels. The para
meter can be set for the individual channels independently of each other.
Bit
Bit 0/1:
Bit 2/3:
Bit 4/5:
Bit 6/7:
Values
Channel 3
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
0
1
Remark
For sensor connection designs see section 4.3.3
Tab. 4/13: Sensor connection designs channel x
4−22
channel 0
channel 1
channel 2
channel 3
Channel 2
Channel 1
0
0
0
0
1
0
1
0
0
1
0
1
1
1
1
1
sensor connection design channel 0
sensor connection design channel 1
sensor connection design channel 2
sensor connection design channel 3
Channel 2
Channel 1
0
0
0
0
1
0
1
0
0
1
0
1
m = module number (0 ... 47)
Channel 0
0
0
0
No measured value
smoothing (presetting)
1
0
1
Smoothing 2 values
0
1
0
Smoothing 4 values
1
1
1
Smoothing 8 values
m = module number (0 ... 47)
Channel 0
0
0
0
2−cable (presetting)
1
0
1
3−cable
0
1
0
4−cable
Festo P.BE−CPX−AX−EN en 0503b

Advertisement

Table of Contents
loading

This manual is also suitable for:

Cpx-2ae-u-iCpx-4ae-iCpx-4ae-tCpx-2aa-u-i

Table of Contents