2. Analogue input module CPX−2AE−U−I
Festo P.BE−CPX−AX−EN en 0503b
Setting the input signal range
You can set the signal range of the relevant analogue input
with the 2−element DIL switches 0 and 1.
Signal
Setting the DIL switches
range
Setting
0 ... 10 V
0 ... 20 mA
4 ... 20 mA
1)
DIL switch 0 for input channel 0
DIL switch 1 for input channel 1
2)
Default (factory setting)
Tab. 2/2:
DIL switches of the analogue input module
2AE−U−I
Please note
The setting of the signal range with the DIL switches can
be modified by parametrizing (see section 2.4). Parame
trizing has precedence over the DIL switch setting.
1)
DIL switch 0
DIL switch 1
2)
0.1: OFF
1.1: OFF
2)
0.2: OFF
1.2: OFF
0.1: ON
1.1: ON
0.2: OFF
1.2: OFF
0.1: OFF
1.1: OFF
0.2: ON
1.2: ON
0.1: ON
1.1: ON
0.2: ON
1.2: ON
2)
2)
2−7