4. Analogue input module CPX−4AE−T
Channel parameters:
4828 + m * 64 + 11 (channel 0)
Function no.
4828 + m * 64 + 12 (channel 1)
4828 + m * 64 + 13 (channel 2)
4828 + m * 64 + 14 (channel 3)
Description
Sets the temperature sensor used for the channels. If necessary, set the tempe
rature range for Pt sensors. The parameters can be set for the individual channels
independently of each other.
Bit
Bit 0 ... 3:
Bit 4 ... 6:
Bit 7:
Values
Bit 7 Bit 6 Bit 5 Bit 4 Bit 3 Bit 2 Bit 1 Bit 0
0
Sensor type Pt sensors:
Sensor type Ni sensors:
Temperature range for Pt sensors:
0
1
Remark
The temperature range can only be set for Pt sensors:
Temperature range standard:
Temperature range climate:
Tab. 4/14: Sensor type/temperature coefficient, temperature range channel x
Festo P.BE−CPX−AX−EN en 0503b
Sensor type/temperature coefficient, temperature range
channel x
sensor type with temperature coefficient (TK)
reserved
temperature range (only for Pt sensors)
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
= not relevant here
m = module number (0 ... 47)
0
0
0
0
0
0
0
1
0
0
1
0
0
0
1
1
0
1
0
0
0
1
0
1
0
1
1
0
0
1
1
1
1
0
0
0
1
0
0
1
1
0
1
0
1
0
1
1
1
1
0
0
− 200 ... + 850 °C (− 328 ... 1562 °Fahrenheit)
− 120 ... + 130 °C (− 184 ... 266 °Fahrenheit)
Channel is deactivated
Pt 100 with TK = 0.00385
(presetting)
Pt 200 TK = 0.00385
Pt 500 TK = 0.00385
Pt 1000 TK = 0.00385
Pt 100 TK = 0.00391
Pt 200 TK = 0.00391
Pt 500 TK = 0.00391
Pt 1000 TK = 0.00391
Ni 100 TK = 0.00617
Ni 120 TK = 0.00617
Ni 500 TK = 0.00617
Ni 1000 TK = 0.00617
Standard (presetting)
Climate
4−23