Festo CPX-AB Series Electronic Manual page 152

Cpx terminal/analogue i/o modules, sub-bases type
Hide thumbs Also See for CPX-AB Series:
Table of Contents

Advertisement

4. Analogue input module CPX−4AE−T
Fault number
15
29
1)
The analogue input signals will, however, be processed further.
2)
Processing of the analogue input signals will be stopped. This error message will be triggered by
the field bus node.
3)
The parameters entered will be ignored, the module operates with the last valid parameters.
Tab. 4/20: Error messages of the input modules part 2
4−30
Description
Module/channel failed
General fault, module faulty.
Fault in parametrizing
A fault has occurred in the setting of a
parameter:
wire fracture
connection design of the sensor
sensor type and temperature range.
Note
Please note the following when using the input modules:
If there is a short circuit, all sensor supplies of the
module will be switched off together.
The sensor power supply will be switched on again
automatically when the short circuit is eliminated.
Fault treatment
2)
Power off/on necessary
·
If this fault occurs again: check
·
and, if necessary, replace the
analogue input module.
Evaluation of the analogue input
signals has stopped.
1) 3)
Check the parametrizing
·
undertaken and, if necessary,
undertake the parametrizing again
with the correct parameters (valid
parameters see section 4.4.3).
The analogue input module will be
operated further with the last valid
parametrizing.
Festo P.BE−CPX−AX−EN en 0503b