Module parameters: Output analogue−value data format
4828 + m * 64 + 3
Function no.
Description
Determines the format in which the digital output words from the output module
are interpreted for the analogue output signals.
Bit
Bit 0...3:
Bit 4, 5:
Bit 6, 7:
Values
Bit 5
0
0
1
1
Remark
The reserved bits 0...3 and 6, 7 must always be 0. If one or several bits are set to
1" during parametrizing, the parametrizing carried out is invalid and therefore
not effective. If the module parameter Monitoring parametrizing faults" is set to
active", the relevant fault will be displayed.
Further information on this parameter can be found in section 5.4.4.
Tab. 5/12: Output analogue−value data format
5−20
m = module number (0 ... 47)
reserved (= 0)
output analogue−value data format
reserved (= 0)
Bit 4
0
VZ + 15 bits linear scaled
1
VZ + 12 bits right−justified (compatible with valve terminal
type 03, presetting)
0
VZ + 15 bits left−justified, linear scaled (Simatic S7)
1
VZ + 12 bits left−justified + diagnosis (Simatic S5)
(VZ = sign)
Festo P.BE−CPX−AX−EN en 0503b