Configuration Data - Beckhoff EL3773 Documentation

Power monitoring oversampling terminal
Table of Contents

Advertisement

6.6.2

Configuration data

Index 80p0 AI Settings (for p = 0...5, corresponding to channel 1...6)
Index (hex) Name
80p0:0
AI Settings
80p0:07
Enable limit [} 87]
80p0:0A
Enable user calibration
[} 87]
80p0:0B
Enable vendor calibra-
tion [} 87]
80p0:13
Limit 1 [} 87]
80p0:14
Limit 2 [} 87]
80p0:15
Filter settings [} 85]
80p0:17
User calibration offset
[} 87]
80p0:18
User calibration gain
[} 87]
The filter characteristics are set via index 0x8000:15
The filter frequencies are set for all channels centrally via index 0x8000:15 (channel 1). All
other corresponding indices 0x80p0:15 have no parameterization function!
Note
Index 80pF AI Vendor data (for p = 0...5, corresponding to channel 1...6)
Index (hex) Name
80pF:0
AI Vendor data
80pF:01
Calibration offset
80pF:02
Calibration gain
EL3773
Meaning
Maximum subindex
Limit 1 enabled
Enabling of the user calibration
Enabling of the vendor calibration
First limit value for setting the status bits
Second limit value for setting the status bits
This object determines the digital filter settings.
The possible settings are sequentially numbered.
0: 200 Hz
1: 500 Hz
2: 1000 Hz
3: 1500 Hz
4: 2500 Hz
5: 5000 Hz
6: 15000 Hz
See note below:
User calibration offset
User calibration gain
Meaning
Maximum subindex
Offset (vendor calibration)
Gain (vendor calibration)
Version: 2.5
Commissioning
Data type
Flags
Default
UINT8
RO
> 24 <
BOOLEAN
RW
FALSE
BOOLEAN
RW
FALSE
BOOLEAN
RW
TRUE
INT16
RW
0
dec
INT16
RW
0
dec
UINT16
RW
2500 Hz (4)
INT16
RW
0
dec
INT16
RW
16384
Data type
Flags
Default
UINT8
RO
> 2 <
INT16
RW
-
INT16
RW
-
dec