Beckhoff EL3773 Documentation page 64

Power monitoring oversampling terminal
Table of Contents

Advertisement

Commissioning
Scan over existing Configuration
Change of the configuration after comparison
With this scan (TwinCAT 2.11 or 3.1) only the device properties vendor (manufacturer), de-
vice name and revision are compared at present! A 'ChangeTo' or 'Copy' should only be
Attention
carried out with care, taking into consideration the Beckhoff IO compatibility rule (see
above). The device configuration is then replaced by the revision found; this can affect the
supported process data and functions.
If a scan is initiated for an existing configuration, the actual I/O environment may match the configuration
exactly or it may differ. This enables the configuration to be compared.
Fig. 73: Identical configuration (left: TwinCAT 2; right: TwinCAT 3)
If differences are detected, they are shown in the correction dialog, so that the user can modify the
configuration as required.
Fig. 74: Correction dialog
It is advisable to tick the "Extended Information" check box to reveal differences in the revision.
Colour
Explanation
green
This EtherCAT slave matches the entry on the other side. Both type and revision match.
blue
This EtherCAT slave is present on the other side, but in a different revision. This other
revision can have other default values for the process data as well as other/additional
functions.
If the found revision is higher than the configured revision, the slave may be used provided
compatibility issues are taken into account.
If the found revision is lower than the configured revision, it is likely that the slave cannot be
used. The found device may not support all functions that the master expects based on the
higher revision number.
light blue
This EtherCAT slave is ignored ("Ignore" button)
64
Version: 2.5
EL3773

Advertisement

Table of Contents
loading

Table of Contents