Fig. 102 Linking Of 2-Bit Variable To Additional Task; Fig. 103 User Settings And Vendor Calibration In The Coe Online Directory - Beckhoff EL3773 Documentation

Power monitoring oversampling terminal
Table of Contents

Advertisement

Commissioning
Fig. 102: Linking of 2-bit variable to additional task
Example of voltage measurement with EL3773:
Channel 1; Limit 1 and Limit 2 enabled, Limit 1 = 100 V, Limit 2 = 200 V, representation: signed integer
Entry in index (Limit 1): 0x8000:13 [} 95]
16
(100 V / 410 V) x 2
/ 2 - 1 = 7991
Entry in index (Limit 2): 0x8000:14 [} 95]
16
(200 V / 410 V) x 2
/ 2 - 1 = 15983
Output:
Input channel 1
Index 0x6000:03 [} 96]
50 V
0x01
100 V
0x03
150 V
0x02
210 V
0x02
4. Provision in the process data
The influencing parameters can be changed in the CoE of the respective channel.
Fig. 103: User settings and vendor calibration in the CoE online directory
88
dec
dec
, (Limit 1, limit value undershot)
hex
, (Limit 1, limit value reached)
hex
, (Limit 1, limit value exceeded)
hex
, (Limit 1, limit value exceeded)
hex
Version: 2.5
Index 0x6000:05 [} 96]
0x01
, (Limit 2, limit value undershot)
hex
0x01
, (Limit 2, limit value undershot)
hex
0x01
, (Limit 2, limit value undershot)
hex
0x02
, (Limit 2, limit value exceeded)
hex
EL3773