Index 0x80n0 AI Settings (n=0: Channel 1, n=1: Channel 2)
Index
Name
(hex)
80n0:0
AI Settings
80n0:01
Enable user scale User scale is active
80n0:06
Enable filter
80n0:07
Enable limit 1
80n0:08
Enable limit 2
80n0:0A
Enable user
calibration
80n0:0B
Enable vendor
calibration
80n0:11
User scale offset
80n0:12
User scale gain
80n0:13
Limit 1
80n0:14
Limit 2
80n0:15
Filter settings
80n0:17
User calibration
offset
80n0:18
User calibration
gain
84
Meaning
Maximum subindex
Enable filter, which makes PLC-cycle-
synchronous data exchange
unnecessary
Limit 1 enabled
Limit 2 enabled
Enabling of the user calibration
Enabling of the vendor calibration
User scaling offset
User scaling gain.
The gain is represented in fixed-point
-16
format, with the factor 2
The value 1 corresponds to 65536
(0x00010000) and is limited to
±0x7FFFF
First limit value for setting the status
bits
Second limit value for setting the status
bits
This object determines the digital filter
settings, if it is active via Enable filter
(index 0x80n0:06).
The possible settings are sequentially
numbered.
0: 50 Hz FIR
1: 60 Hz FIR
2: IIR 1
3: IIR 2
4: IIR 3
5: IIR 4
6: IIR 5
7: IIR 6
8: IIR 7
9: IIR 8
User offset compensation
User calibration gain
Version: 1.2
Data type
UINT8
BOOLEAN RW
BOOLEAN RW
BOOLEAN RW
BOOLEAN RW
BOOLEAN RW
BOOLEAN RW
INT16
INT32
.
dec
INT16
INT16
UINT16
INT16
INT16
Flags Default
RO
0x18 (24
)
dez
0x00 (0
)
dez
0x00 (0
)
dec
0x00 (0
)
dez
0x00 (0
)
dez
0x00 (0
)
dez
0x00 (0
)
dez
RW
0x0000 (0
)
dez
RW
0x00000000
(0
)
dez
RW
0x0000 (0
)
dez
RW
0x0000 (0
)
dez
RW
0x0000 (0
)
dec
RW
0x0000 (0
)
dez
RW
0x4000
(16384
)
dec
EL3182