C. EtherNet/IP Objects of the CPX-FB36
C.4.6 General Module Parameter Object
Procedure for
parameterisation
C-28
Object class:
Instances:
Applicable is: Instance number = Module number + 1
This Object enables general access to the module parameters
of all existing and future CPX modules.
Use this Object for parameterising modules with word or
double-word parameters.
Examples of modules with word or double-word parameters:
– analogue 4-input module CPX-4AE-I
– temperature module CPX-4AE-T
– CPX-CP interface
You can access three types of parameters via the Attributes of
the general Module Parameter Object:
– byte parameters
– word parameters
– double-word parameters through the Attribute 129 ... 189
1. Refer to the module manual for the function number of
the parameter which you wish to set.
2. Search for this function number in the last column of
Tab. C/30 (byte and word parameter) or Tab. C/31
(double-word parameter)
3. Read the appropriate Attribute number from the table.
Examples for parameterisation with the general Module Para-
meter Object can be found in section C.5.2.
101
d
1 ... 48
through the Attribute 1 ... 64
through the Attribute 65 ... 127
Festo P.BE-CPX-FB36-EN en 1309NH English