Cpx Status Information (Group A - Festo CPX-FB36 Electronics Description

Terminal cpx
Hide thumbs Also See for CPX-FB36:
Table of Contents

Advertisement

D. Modbus/TCP Objects of the CPX-FB36
D.3

CPX status information (group A)

Modbus
CPX terminal configuration
address
Processing data inputs
Bit 15
14
45367
Module 0 ... 15
45368
Module 16 ... 31
45369
Module 32 ... 47
Bit n = 0: Module does not exist
Bit n = 1: Module exists
Tab. D/2:
Configuration information on the modules of the CPX terminal
Modbus
Error detection
address
Processing data inputs
Bit 15
14
45383
Module 0 ... 15
45384
Module 16 ... 31
45385
Module 32 ... 47
Bit n = 0: No fault
Bit n = 1: Fault in module n
Tab. D/3:
Reognition, which module registers a fault
D-4
The status information provides information on the configura-
tion and the fault status of the CPX terminal. It lies in the
Modbus address range 45367 to 45391.