B. Address assignment of the CPX terminal
B.2
Addressing
Sequence of addressing
1.
I/O diagnostics interface
2.
Analogue modules
3.
Technology modules
4.
Digital modules
1) Depending on the setting, this address range can also be occupied by status bits (
and Tab. 1/2).
Tab. B/10: Sequence of addressing
B-14
Basic rules for addressing
The address assignment of the inputs does not depend on
the address assignment of the outputs.
Counting from left to right, addressing bytewise: Modules
with less than 8 bits occupy an 8-bit address space, but
do not use it completely.
The bus node counts as a module with 0 inputs and 0 out-
puts when the status bits and the I/O diagnostic interface
are deactivated.
The I/Os of different module types are assigned separ-
ately from each other.
The sequence in the following table applies:
Description
1)
Can be activated by DIL switch. If the interface is activated, it
will occupy the first 16 inputs and outputs in the address
range.
Modules with analogue inputs/outputs
e.g. CP interface, Front End Controller CPX-FEC
Modules with digital inputs/outputs
Festo P.BE-CPX-FB36-EN en 1309NH English
Note above