2. Preparing for commissioning
Festo P.BE-CPX-FB36-EN en 1309NH English
Note
QuickConnect only works if this function is supported by
all participating devices.
Make sure that intermediate switches and routers in
•
your network support this function.
Using QuickConnect:
Deactivate Auto-Negotiation in the bus node for both net-
•
work connections X1 and X2.
–
Baud rate = 100 Mbit/s
–
Duplex mode = Full-Duplex
Attribute 6
face Control).
Deactivate Auto-Negotiation and crossover detection for
•
the corresponding network connection of the counterpart
station (e.g. switch connection).
–
Baud rate for connection of the counterpart station =
100 Mbit/s
–
Duplex mode = Full-Duplex
Activate QuickConnect via attribute 12 of the TCP/IP inter-
•
face object. (The QuickConnect function in the bus node is
in a deactivated state when delivered.)
Activate QuickConnect in the PLC or in the control pro-
•
gram.
Simplified configuration of QuickConnect on CPX-FB36:
Set the CPX parameter "IP configuration" to
•
"With saved parameters and QuickConnect".
Selecting this setting activates QuickConnect and deactivates
Auto-Negotiation for both network connections.
of the Ethernet link object (Inter-
d
2-5