Profibus Configuration Of The Gateway - How The Data Are Transferred - Leuze electronic MSI 400 Series Manual

Hide thumbs Also See for MSI 400 Series:
Table of Contents

Advertisement

Step 1: Check target address
Ä Ensure that the desired address (byte 23 in our example) has not been allocated.
Ä When the target address is assigned here, delete the bytes placed there.
To do this, click on the byte in the work area and click on the Delete symbol in the command bar.
Step 2: Delete byte from original address
Ä Delete the byte you wish to reallocated (byte 1 in our example).
To do this, click on the byte in the work area and click on the Delete symbol in the command bar.
Step 3: Place byte on new target address
Ä Open the Gateway docking window and select the desired bytes under the associated module.
Ä Use the mouse button to drag the Byte into the work area on byte 23.
9.3

PROFIBUS configuration of the gateway - how the data are transferred

The following steps are required to configure the communication between the PLC and the gateway.
NOTICE
i
This documentation does not address the installation of the PROFIBUS-DP network or the other
components of the automation system project in the network configuration tool. It is assumed
that the PROFIBUS project in the configuration program, e.g. the SIEMENS SIMATIC Manager,
has already been set up. The examples presented are based on configurations created with the
help of the SIEMENS SIMATIC Manager.
Step 1: Install the device master file (GSD)
Before the MSI-FB-PROFIBUS can be used for the first time as part of the network configuration tool, e.g.
the SIEMENS SIMATIC Manager, the device master file (GSD) of the gateway must first be installed in the
hardware catalog of the tool.
Leuze electronic
MSI 400
PROFIBUS DP gateway
106