LED
PWR
Tab. 9.2:
Address switch of the MSI-FB-PROFIBUS module
Switches
× 10
× 1
How to set the PROFIBUS-DP address with the aid of the hardware address switches:
Ä Use the hardware address switches at the front of the system to set the PROFIBUS-DP address.
Ä Switch the MSI 400 system off and on again.
How to set the PROFIBUS-DP address in the software:
Ä Set the two hardware address switches on the front of the device to "00".
Ä Launch MSI.designer.
Ä Read in the hardware configuration, including the PROFIBUS-DP gateway.
Instructions: Software manual, chapter "Connecting to the safety controller"
Ä Open the Modules docking window and select the MSI-FB-PROFIBUS module.
Ä Also open the Properties docking window.
ð You see the configuration dialog for the MSI-FB-PROFIBUS module.
Ä Enter the desired value for the Control address parameter under Communication.
Leuze electronic
Meaning
No power supply
Off
Power supply switched on, no error
Green
Critical error
Red
Function
Address switch 1
Rotary switch with 10 positions for setting the module address
(in tens)
Address switch 2
Rotary switch with 10 positions for setting the module address
(in units)
MSI 400
PROFIBUS DP gateway