Leuze electronic MSI 400 Series Manual page 141

Hide thumbs Also See for MSI 400 Series:
Table of Contents

Advertisement

Error
CAN-Tx-Fifo
overflow
The CAN con-
trols have no
transmission
resources
CAN initializa-
tion failed.
The CAN con-
trols could not
be initialized
CANopen Life
Guarding
CANopen Life
Guarding has
found a cable
break
Leuze electronic
Internal
Error type Emergency er-
safety bus
error code
0x4506
Warning
0xC507
Critical
0x4508
Warning
Error his-
ror code
tory
SDO 1003
Error register
M1...M5
0x8110
0x11
2, 0, 0, 0, 0
0x8130
0x11
0, 0, 0, 0, 0
MSI 400
CANopen gateway
Results/possible remedy
CAN messages that were to
be sent from the gateway
have been lost. The number
of events for which the gate-
way is to send CAN mes-
sages is too high for the set
baud rate.
• Increase the baud rate or
change the configuration
of the gateway.
The CAN controls or the
transceiver may be defective.
• Replace the MSI-FB-
CANOPEN module with a
new device.
The gateway has generated a
life guarding error message:
Either an error has occurred
on the node guarding or the
heartbeat NMT master or the
CAN cable has been interrup-
ted.
• Check the CANopen mas-
ter.
• Check the cabling.
141