For the MSI-FB-PROFIBUS gateway, data set 1 was divided into five input data blocks, with data
blocks 1–4 each containing 12 bytes and data block 5 two bytes.
For the MSI-FB-CANOPEN gateway, data set 1 was divided into four blocks, each with 8 bytes.
You will find more detailed information in the corresponding section for each gateway.
• Data set 2 (32 bytes) contains the test values (CRCs) for the system configuration.
See table "Overview of input data sets 1-3 (basic settings for Modbus TCP)" below
• Data set 3 (60 bytes) contains the state and diagnostic data for the various modules, with four (4) bytes
per module, with the controller module comprising 3 x 4 bytes. Details: see table "Meaning of module
state bits" [chapter 3.3.5]
• Data set 4 (60 bytes) is currently filled with reserved values.
The following table provides an overview of which data sets are provided by which gateway.
Tab. 3.3:
Availability of data sets 1–4
MSI 430
MSI-FB-ETHER-
CAT
MSI-FB-PROFIBUS PROFIBUS DP
MSI-FB-CANOPEN CANopen
1)
The MSI-FB-CANOPEN is used to provide diagnostic data via CANopen SDO (service data objects).
More information about how to provide state and diagnostic data with the aid of the CANopen gateway
may be found here: CANopen gateway [chapter 10]
2)
Readable with instance 2 of class 120
3)
Readable with instance 3 of class 120 and byte 52 to 111 of assembly 167
Tab. 3.4:
Overview of input data sets 1–3 (basic setting for Modbus TCP)
Data set 1
Byte 0
Input values for Module 0
(I1..I8)
Byte 1
Input values for Module 0
(I9..I16)
Byte 2
Input values for Module 0
(IQ1..IQ4)
Byte 3
Output values for Module 0
(Q1..Q4, IQ1..IQ4)
Byte 4
Direct data (Off) 0
Byte 5
Direct data (Off) 1
Byte 6
Direct data (Off) 2
Byte 7
Direct data (Off) 3
Leuze electronic
Data set 1
Data set 2
Modbus TCP
Modbus TCP
PROFINET IO
PROFINET IO
EtherNet/IP
EtherNet/IP
EtherCAT
EtherCAT
CANopen (SDOs)
Data set 2
Project CRC
System CRC
(PROFIBUS
DP and Eth-
erCAT)
Data set 3
Modbus TCP
PROFINET IO
EtherNet/IP
EtherCAT
1)
CANopen (SDOs)
Data set 3
Module state MSI 4xx
Module state MSI 4xx
Test pulse comparison, control-
ler module inputs
Test pulse comparison, control-
ler module inputs
Test pulse comparison, control-
ler module inputs
State of two-channel controller
module inputs
State of two-channel controller
module inputs
Reserved
MSI 400
Product description
Data set 4
Modbus TCP
PROFINET IO
-
1)
Data set 4
Reserved
15