The IP address is assigned in two steps.
Ä Assign a unique system-specific name to the Gateway, using either the network configuration tool such
as SIEMENS TIA Portal, or using the MSI.designer software. In MSI.designer this is the Connection
name.
Where do you edit the connection name in MSI.designer? Open the Project structure docking window
and there click on the Controller entry right at the top. Additionally open the Properties docking win-
dow and enter the desired value there in the configuration dialog under Connection name.
Ä A (unique) system-specific name can be used by the I/O-Controller (i.e. the PLC) to assign the IP ad-
dress to the gateway now before the system is booted.
NOTICE
i
The MAC address of the MSI 430 module is printed on the device's nameplate (Example:
00:07:17:02:03:05).
Using the Siemens TIA Portal to assign device names
In the Online accesses area, select the network card connected to the network which can be used to ac-
cess the MSI 430 device. In the Assign name function area, edit the PROFINET device name field and
then select Assign name.
This will permanently assign the new device name to the MSI 430 device.
Fig. 7.10:
Assigning device names with the TIA portal
Assign device name via the software
Ä Launch MSI.designer and connect to the controller module MSI 430.
Ä Press the Stop button in the Modules view to stop the application.
Ä In the Modules view click on the blue background and open the Properties docking window.
ð You will see the controller configuration dialog.
Ä Edit the connection name and click the Send button.
Fig. 7.1:
Configuration dialog for the IP data and the device name
Leuze electronic
MSI 400
PROFINET IO-Gateway