8

EtherNet/IP gateway

This chapter describes the "EtherNet/IP-Gateway" function of the MSI 430 module.
The EtherNet/IP protocol is not described in this chapter. If you have little or no experience with this, please
refer to the ODVA documentation for more information. Some content can be found in the glossary (see
Abbreviations and Definitions [chapter 1.5]).
NOTICE
i
Use of the term "Device" in this chapter
This chapter uses the term "Device" as a synonym for the controller module MSI 430.
8.1

Interfaces and operation

Interfaces and operation are identical to that of the Modbus TCP Gateway.
Read the following section: Interfaces and operation [chapter 6.1]
8.2

Datasheet

The MSI 430 module supports EtherNet/IP from product version D-01.01. The following functions are integ-
rated:
• Implicit message transmission (transport class 1)
• Explicit message transmission (transport class 3, connected)
• Device profile: Discrete universal I/O device
• UCMM Message Server (no connection)
• Supported objects: Message router, connection manager, port, identity, Ethernet link, TCP/IP, I/O point
and group (discrete), vendor class 0x78, assembly
• Up to five simultaneous encapsulation sessions (input and output)
• Assemblies of a variable size
• Supported addressing: Class/instance/attribute and symbol tag
• Agreement with CIP (Common Industrial Protocol) specification and with EtherNet/IP CIP specification,
according to table Module versions and referenced specification versions for EtherNet/IP [chapter 8.2]
• Details EDC file with ODVA conformity test
• Supported PCCC commands: Read and write word range, read and write input, read and write protec-
ted logic input with two and three address fields for connection to PLC 3, PLC 5, PLC 5/250, PLC 5/
VME, SLC 500, SLC 5/03, SLC 5/04 and MicroLogix-1000
• Automatic configuration of semi and full duplex connections as well as of connections with 10 and 100
Mbit/s.
• MS (module state) and NET (network) LED
Tab. 8.1:
Module versions and referenced specification versions for EtherNet/IP
Module version
up to D-01
from D-03
8.3

Basic setup

8.3.1

Basic configuration of PLC

This chapter briefly describes the basic configuration of the PLC.
Firstly, install the current EDS file for the MSI 430 module in your PLC configuration program. You can find
the current EDS file on the Internet at http://www.leuze.com. The following diagram shows you how you
can make the setting using the Logix Designer.
Leuze electronic
CIP (Common Industrial Pro-
tocol) specification
Version 3.18
Version 3.21
MSI 400
EtherNet/IP gateway
EtherNet/IP CIP specification
Version 1.19