The first relevant byte for the module 2 error described above is module state byte 0 for module 2. This is
byte 11 with the hexadecimal value FB (1111 1011):
Bit #
Value
This corresponds to the error message "Summary of bits 0.5 to 0.7 (external error)", byte 0, bit 2 in the fol-
lowing table: "Meaning of module state bits of the secure I/O modules" [chapter 3.3.5]
The second relevant byte is the module state byte 3 for module 2. This is byte 08 with the hexadecimal
value EF (1110 1111):
Bit #
Value
This corresponds to the error message "Short circuit monitoring of output 3, short circuit after high", byte 3,
bit 4 in the following table: "Meaning of module state bits of the secure I/O modules" [chapter 3.3.5]
NOTICE
i
Ä Reserved (for future use) = static 1 (no state change)
Ä Not used (can be 0 or 1 ), both values occur.
Ä If there is no module, all values - including the reserved values - are set to logical 1.
Leuze electronic
00
01
02
03
...
11
FF
FF
FF
FF
Status of controller mod-
ule
7
6
1
1
7
6
1
1
04
05
06
07
12
13
14
15
FF
FF
FF
FF
Status of module 1 (MSI-
EM-IO84)
5
4
1
1
5
4
1
0
MSI 400
Product description
08
09
10
11
16
17
18
19
EF
FF
FF
FB
FB
EF
State of module 2 (MSI-
EM-IO84)
3
2
1
1
0
1
3
2
1
1
1
1
...
...
...
0
1
0
1
22