Instance Byte
167
0 to 49
50
51
52 to 111 Read
The data type of supported assemblies is BYTE which means strings of 8 bits each. The naming in Logix
Designer is SINT, which has the same size of 8 bits each.
If PLC requires a configuration assembly, any value or blank can be used for assembly instance. Size of
the configuration assembly shall be zero.
Please use assembly instances from Table "Overview of Assembly data bytes [chapter 8.5.1]" for Input
and Output. These settings can be used in generic EtherNet module configuration in Logix Designer which
can be seen in the illustration below.
Fig. 8.25:
Generic Ethernet module configuration
Leuze electronic
Access Data type
Description
Read
BYTE[50]
Logic output bytes, configura-
tion via Output data block 1 in
MSI.designer (see [chapter
8.5.3])
Read
BYTE
Bit 7: Input state
Bit 6: Output state
Bit 5: Error code ≠ 0
Read
BYTE
System mode
BYTE[60]
State bytes of the controller
module (Instance 3 of class 120
[chapter 8.4.8.3]), output data
set 3 (siehe [chapter 8.5.3])
MSI 400
EtherNet/IP gateway
Size
Data range
1 to 50
0 to 0xff
Bytes
1 byte
0x00, 0x40,
0x80, 0xc0
1 byte
1, 2, 3, 4, 5,
7, 21
60 byte
0 to 0xff
90