Name
Total Transaction
Address
Type ID
The answer of the MSI 430 module does not contain any data, only a state, see table PCCC reply header
[chapter 8.4.7.1]. The UINT data format corresponds to writing the format of the word range.
Tab. 8.18:
Write address structure of PLC-5 input
Address
Data type
$N37:x
UINT[n]
$N138:x
UINT[n]
$N139:x
UINT[n]
$N140:x
UINT[n]
$N141:x
UINT[n]
The data range of the number of elements is relative to the assembly sizes. See the table Overview of as-
sembly databytes of the MSI 430 module [chapter 8.5.1]
8.4.7.5
Typed Read
The MSI 430 module supports "Read PLC-5 input" according to the following table:
Tab. 8.19:
Read request data structure of PLC-5 word range
Name
Packet offset
Total Transaction
Address
Size
The answer of the MSI 430 module is listed in the following table. The first byte of the type ID is 0x9a =
0b1001 1010, meaning that the data type is given in the following byte and the data size in the byte after
that. The fourth byte of the type ID is 0x42 = 0b0100 0010, standing for an integer data type of size 2.
Leuze electronic
Data type
Description
UINT
Number of elements in the transaction
BYTE[m]
PLC-5 system address, m >= 2
BYTE[n]
Data type and size, n >= 1
Number of
Description
elements
n
Output assembly of the device profile Discrete
universal I/O device, x = 0 to 24, n = 25 - x
n
Output assembly of the logic output, con-
figured via the input data block 2 to 5 in
MSI.designer,
x = 0 to 19, n = 20 – x
n
Output assembly of the logic output, con-
figured via the input data block 3 to 5 in
MSI.designer,
x = 0 to 14, n = 15 – x
n
Output assembly of the logic output, con-
figured via the input data block 4 to 5 in
MSI.designer,
x = 0 to 9, n = 10 – x
n
Output assembly of the logic output, con-
figured via the input data block 4 to 5 in
MSI.designer,
x = 0 to 4, n = 5 – x
Data type
Description
UINT
Offset in number of elements
UINT
Number of elements in the transaction
BYTE[m]
PLC-5 system address, m >= 2
UINT
Number of elements to be returned
MSI 400
EtherNet/IP gateway
Data range
See next table
Data range
0 to 65535
0 to 65535
0 to 65535
0 to 65535
0 to 65535
Data range
0 to value dependent on the
assembly size
"0" to ":", "A" to "Z", "a" to "z"