Double sheet detector with integrated fieldbus interface
Hide thumbs Also See for R1000 Series:
Table of Contents

Advertisement

Communication with the PLC
6.4.5
Service "Write parameters"
Initiate the master with the setting of the service selection, the index bytes I1 and I2. The content of
the application data bytes 0 to 3 are also stored. The checksum of byte 1 through 6 is calculated
and inserted in byte 7. To initiate the service the master changes the handshake bit.
In order to avoid data faults the following sequence is compulsory:
1.
Service selection, program index, parameter index, application data byte 0 to 3
2.
Switch handshake
In addition consistent data communication from the master is necessary.
The R1000 checks the data with the checksum and transfers the content of the application data
bytes of the parameter channel I3 ... I6 into its own parameter memory. Afterwards the R1000
mirrors the index adjustment in O1, O2 and the application data in O3 ... O6. Only in the last step
inserts the R1000 the handshake bit in O0.0 and indicates thereby that the data has been
completely accepted. The same sequence applies here also, in order to avoid data faults.
The slave should ensure a consistent data transmission.
6.4.6
Service "Empty service"
The master initiates the service "Empty service" with the setting of the service selection. The
content of the index bytes I1, I2 and the application data bytes 0 to 3 are not relevant. The
checksum of byte 1 through 6 is calculated and inserted in byte 7. To initiate the service the master
switches the handshake bit.
In order to avoid data faults the following sequence is compulsory:
1.
Service selection, program index, parameter index, application data byte 0 to 3
2.
Switch handshake
In addition consistent data communication from the master is necessary.
The R1000 checks the data with the checksum and mirrors the index adjustment in O1, O2 and the
application data in O3 ... O6. A possibly set collision bit is set back. Only in the last step inserts the
R1000 the handshake bit in O0.0 and indicates thereby that the data has been completely
accepted. The same sequence applies here also, in order to avoid data faults.
The slave should ensure a consistent data transmission.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
90
Double Sheet Detector R1000 series UDK20
with integrated fieldbus interface
Attention
If writing cannot be executed, the collision bit is set. In place of the
application data a fault number is transmitted,
see section "6.4.8 Reset faulty access".
Attention
If the service "Empty service" cannot be executed, the collision bit is
set (remains set). In place of the application data a fault code is
transmitted, see section "6.4.8 Reset faulty access".
Manual
B0048191 / Rev. 1.5