Start-up
System parameter 17: Setting the output logic (0-sheet, 1-sheet, 2-sheet outputs).
system parameter
output 0-1-2:
Fig. 84: Setting the output logic
Possible choices:
0 V:
+24 V: The outputs 0-sheet, 1-sheet and 2-sheet are inverted, i.e. the respective signals in
System parameter 18: Deactivating / activating the external calibration via fieldbus.
system parameter
ext. adjust:
Fig. 85: Deactivating / activating the external calibration
Here the external calibration, which is possible via fieldbus with the signals "Teach-In" and "zero
adjust", can be deactivated / activated.
System parameter 19: Diagnostic factors.
This system parameter is used for the equipment diagnostics and should not be changed by the
user.
system parameter
diagnostic factors
Fig. 86: Diagnostic factors (fixed)
system parameter
P12 LW: 24-32ms/m
Fig. 87: Indicating the investigated conductance
Here the conductivity investigated for this program is shown (here: program 12)
Extra: = slightly magnetical NF material
FE = magnetical steel
For NF material the conductivity range is shown.
With the ENTER key and UP/ DOWN keys all programs can be polled / indicated.
The ENTER key will exit the section.
The UP key leads to the following menu item:
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
120
Double Sheet Detector R1000 series UDK20
with integrated fieldbus interface
17
0V
As shown in the timing diagrams and the wiring diagrams
the timing diagrams and wiring diagrams must be seen inverted.
Note
The outputs "Enable" and "Warning" are not affected thereby.
18
no
19
19
Manual
B0048191 / Rev. 1.5