Roland R1000 Series Manual page 127

Double sheet detector with integrated fieldbus interface
Hide thumbs Also See for R1000 Series:
Table of Contents

Advertisement

B0048191 / Rev. 1.5
16
The control unit shows the measured thickness in the display.
General rules for monitoring ferrous material (steel that can be magnetized) and non-ferrous
materials (aluminum, non-magnetic stainless steel, slightly magnetic non-ferrous material):
• FE:
The measured value should not deviate by more then 5%, (max. 10% with coated sheets,
exceeding 10% with nickel) from the actual thickness of the measured sheet. If it deviates
more, then the cause could be a wrong sheet thickness or an air gap, which has to be
eliminated (do not use bowed sheet for teaching). The measured value must now be
adjusted to the actual sheet thickness.
NF and LM (slightly magnetic material):
The measured value must be adjusted to the actual sheet thickness
17
Confirm the Teach-In and adjustment with the ENTER key and exit the menu "programming".
Example: Nominal thickness 2.00 mm
The micrometer measures actual value to be: 1.92 mm.
The Teach-In shows a value of: 1.89 mm.
The display value must now be corrected to 1.92 mm.