Roland R1000 Series Manual page 78

Double sheet detector with integrated fieldbus interface
Hide thumbs Also See for R1000 Series:
Table of Contents

Advertisement

Communication with the PLC
Waiting for "Function fault"
In case of "Function fault":
- Pause 100 ms
- Set "Measurement start" to LOW
- Reset "Function fault"
Explanation:
If a fault occurs when initiating the function (for instance a previous function is still active)
then only the "Function fault" is displayed. The "Function result" will not be displayed. The
other outputs remain in their current status.
If the fault occurs during execution, the "Function fault" is displayed. The "Function result" will
not be displayed (if the fault is connected to the function). The outputs remain in their current
status.
If the fault occurs after the result, for instance, by a faulty operation then this has no
influence on the "Function result".
If the "Measurement start" cycle is shorter than the duration of the function then the
"Function result" will not be displayed. However, the function is nevertheless executed ! For
safety reason the control should not be executed in this fashion !
If the "Measurement start" cycle is longer than the duration of the function then the "Function
result" will be displayed as shown in the timing diagram.
ROLAND ELECTRONIC GmbH · Otto-Maurer-Str. 17 · DE 75210 Keltern · Phone +49 (0)7236-9392-0 · Fax +49 (0)7236-9392-33
78
Double Sheet Detector R1000 series UDK20
with integrated fieldbus interface
Set "Measurement start" to HIGH
Note
Faults which are not critical can be deleted via the process channel with
the "Reset function fault" command.
Note
The measured timing periods were determined with 12 Mbit- Profibus.
These timing periods can vary with different transmission rates and bus
systems. The cycle time of the PLC has not been taken into account.
Manual
or
Waiting for "Function result"
In case of "Function result":
- Analyze
- Set "Measurement start" to LOW
B0048191 / Rev. 1.5

Advertisement

Table of Contents
loading

This manual is also suitable for:

R1000 udk20

Table of Contents