6.7.4.3
Configuration data (vendor-specific)
Index 80nF PMX vendor data (for ch.1, n = 0; ch.2, n = 1; ch.3, n = 2)
Index (hex) Name
80nF:0
PMX Vendor data
80nF:11
Calibration Voltage
Offset
80nF:12
Calibration Voltage
Gain
80nF:13
Calibration Voltage
Phase Offset
80nF:14
Calibration Current
Offset
80nF:15
Calibration Current
Gain
80nF:16
Calibration Current
Phase Offset
80nF:17
Calibration Current 1
Offset
80nF:18
Calibration Current 1
Gain
80nF:19
Calibration Current 1
Phase Offset
80nF:1A
Calibration Current 2
Offset
80nF:1B
Calibration Current 2
Gain
80nF:1C
Calibration Current 2
Phase Offset
6.7.4.4
Input data
Index 60n0 PMX status (n = 0, 1, 2)
Index (hex) Name
60n0:0
PMX Status
60n0:01
Voltage Sign Bit
60n0:02
Overvoltage
60n0:03
Overcurrent
60n0:04
Inaccurate Voltage
60n0:05
Inaccurate Current
60n0:06
Voltage Guard Warn-
ing
60n0:07
Voltage Guard Error
6000:10
TxPDO Toggle
Index 60n1 PMX Basic (n = 0, 1, 2)
Index (hex) Name
60n1:0
PMX Basic
60n1:11
Voltage
60n1:12
Current
EL34xx
Meaning
Max. subindex
Value in V
Factor (without unit)
Value in milliseconds
Value in A
Factor (without unit)
Value in milliseconds
Value in A
Factor (without unit)
Value in milliseconds
Value in A
Factor (without unit)
Value in milliseconds
Meaning
Max. subindex
Indicates the sign of the current sine wave voltage:
1 = U > 0V
0 = U < 0V
Maximum measurable voltage is exceeded.
Maximum measurable current is exceeded.
The measured voltage value is smaller than the value
entered in CoE object "F800:15 Inaccurate Threshold
Voltage".
The measured current value is smaller than the value
entered in CoE object "F800:16 Inaccurate Threshold
Current".
A warning limit of the voltage monitor has been
breached.
An error limit of the voltage monitor has been
breached.
The TxPDO toggle is toggled by the slave when the
data of the associated TxPDO is updated.
Meaning
 Max. Subindex
 RMS value of the voltage in V
 RMS value of the current in A
Version: 1.5
Commissioning
Data type
Flags
Default
UINT8
RO
0x1C (28
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
1,000000
(1,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
1,000000
(1,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
1,000000
(1,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
1,000000
(1,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
Data type
Flags
Default
UINT8
RO
0x10 (16
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
Data type
Flags
Default
UINT8
RO
0x12 (18
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
)
dez
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
217

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents