Beckhoff EL34 Series Documentation page 194

3-phase energy and power measurement terminals
Table of Contents

Advertisement

Commissioning
Index F80F PM Vendor data
Index (hex) Name
F80F:0
PMX Vendor data
F80F:11
Type
Index F902 PMX Total Info data Power
Index (hex) Name
F902:0
PMX Total Info data
Power
F902:11
Active Power Avg
F902:12
Active Power Min
F902:13
Active Power Max
F902:14
Apparent Power Avg
F902:15
Apparent Power Min
F902:16
Apparent Power Max Maximum total apparent power in the last interval in
F902:17
Reactive Power Avg
F902:18
Reactive Power Min
F902:19
Reactive Power Max
Index F903 PMX Total Info data Energy
Index (hex) Name
F903:0
PMX Total Info data
Energy
F903:11
Active Energy
F903:12
Positive Active En-
ergy
F903:13
Negative Active En-
ergy
F903:14
Apparent Energy
F903:15
Positive Apparent En-
ergy
F903:16
Negative Apparent
Energy
F903:17
Reactive Energy
F903:18
Positive Reactive En-
ergy
F903:19
Negative Reactive
Energy
Index F904 PMX Total Info data PQF
Index (hex) Name
F904:0
PMX Total Info data
PQF
F904:11
PQF Avg
F904:12
PQF Min
F904:13
PQF Max
194
Meaning
Max. subindex
Vendor-specific data
Meaning
Max subindex
Average total active power during the last interval in
W
Minimum total active power in the last interval in W
Maximum total active power in the last interval in W
Average total apparent power during the last interval
in VA
Minimum total apparent power in the last interval in
VA
VA
Average total reactive power average during the last
interval in var
Minimum total reactive power in the last interval in
var
Maximum total reactive power in the last interval in
var
Meaning
Max. subindex
Recorded total active energy in mWh
Received total active energy in mWh
Supplied total active energy in mWh
Recorded total apparent energy in mWh
Received total apparent energy in mWh
Supplied total apparent energy in mWh
Recorded total reactive energy in mWh
Received total reactive energy in mWh
Supplied total reactive energy in mWh
Meaning
Max. subindex
Average value of the power quality factor during the
last interval
Minimum power quality factor in the last interval
Maximum power quality factor in the last interval
Version: 1.5
Data type
Flags
Default
UINT8
RO
0x11 (17
UINT32
RW
0x00000000 (0
Data type
Flags
Default
UINT8
RO
0x19 (25
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
Data type
Flags
Default
UINT8
RO
0x19 (25
INT64
RO
UINT64
RO
UINT64
RO
INT64
RO
UINT64
RO
UINT64
RO
INT64
RO
UINT64
RO
UINT64
RO
Data type
Flags
Default
UINT8
RO
0x13 (19
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
EL34xx

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents