Beckhoff EL34 Series Documentation page 20

3-phase energy and power measurement terminals
Table of Contents

Advertisement

Product overview
EL3443-00xx
Technical data
EL3443-0000
Number of inputs
3 x current, 3 x voltage
Technology
3-phase power measurement
Oversampling factor
Distributed clocks
Optional (for determining the zero crossing time)
Activation interval
one mains period (20 ms at 50 Hz)
Measured values
Current, voltage, active power, reactive power, apparent power, active energy, reactive energy, apparent
energy, cos φ, frequency, THD, harmonics (up to 40th harmonic), power quality factor
Measuring voltage
max. 480 V AC 3~ (ULX-N: max. 277 V AC; max 240 V DC)
Measuring current
max. 1 A (AC/DC),
via measuring transform-
ers x A/1 A
Measuring error
0.3% relative to the full scale value (U/I),
0.6% calculated values (see documentation)
Threshold frequency
3000 Hz
Electrical isolation
2500 V
Update time
mains-synchronous
Current consumption
power contacts
Current consumption via
typ. 120 mA
E-bus
Special features
Single-phase operation possible, mains monitoring functionality, precise voltage zero crossing determina-
tion
Weight
approx. 75 g
Dimensions (W x H x D)
approx. 15 mm x 100 mm x 70 mm (width aligned: 12 mm)
Mounting
on 35 mm mounting rail according to EN 60715
Permissible ambient tem-
-25°C ... +60°C (extended temperature range)
perature range during op-
eration
Permissible ambient tem-
-40°C ... +85°C
perature range during
storage
Relative humidity
95 % no condensation
Vibration / shock resis-
conforms to EN 60068-2-6 / EN 60068-2-27
tance
EMC immunity / emission conforms to EN 61000-6-2/EN 61000-6-4
Protect. class / installation
IP20/any
pos.
Approvals
CE
20
EL3443-0010
EL3443-0011
max. 5 A (AC/DC),
max. 100 mA (AC/DC),
via measuring transform-
via measuring transform-
ers x A/5 A
ers x A/5 A
Version: 1.5
EL3443-0013
max. 333 mV (AC/DC),
via measuring transform-
ers x A/333 mV
EL34xx

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents