Beckhoff EL34 Series Documentation page 184

3-phase energy and power measurement terminals
Table of Contents

Advertisement

Commissioning
Index (hex) Name
F802:0
PMX Guard Settings
F802:11
Frequency Guard Min
Error
F802:12
Frequency Guard Min
Warning
F802:13
Frequency Guard
Max Warning
F802:14
Frequency Guard
Max Error
F802:15
Neutral Current Guard
Min Error
F802:16
Neutral Current Guard
Min Warning
F802:17
Neutral Current Guard
Max Warning
F802:18
Neutral Current Guard
Max Error
F802:19
Active Power Guard
Min Error
F802:1A
Active Power Guard
Min Warning
F802:1B
Active Power Guard
Max Warning
F802:1C
Active Power Guard
Max Error
F802:1D
Apparent Power
Guard Min Error
F802:1E
Apparent Power
Guard Min Warning
F802:1F
Apparent Power
Guard Max Warning
F802:20
Apparent Power
Guard Max Error
F802:21
PQF Guard Min Error Lower limit value for a power quality factor error mes-
F802:22
PQF Guard Min
Warning
F802:23
PQF Guard Max
Warning
F802:24
PQF Guard Max Error Upper limit value for a power quality factor error mes-
F802:25
Unbalance Guard Min
Error
F802:26
Unbalance Guard Min
Warning
F802:27
Unbalance Guard
Max Warning
184
Meaning
Max. subindex
Lower limit value for a frequency error message
Lower limit value for a frequency warning message
Upper limit value for a frequency warning message
Upper limit value for a frequency error message
Lower limit value for an error message of the neutral
conductor current
Lower limit value for a warning message of the neu-
tral conductor current
Upper limit value for a warning message of the neu-
tral conductor current
Upper limit value for an error message of the neutral
conductor current
Lower limit value for an active power error message
Lower limit value for an active power warning mes-
sage
Upper limit value for an active power warning mes-
sage
Upper limit value for an active power error message
Lower limit value for an apparent power error mes-
sage
Lower limit value for an apparent power warning
message
Upper limit value for an apparent power warning
message
Upper limit value for an apparent power error mes-
sage
sage
Lower limit value for a power quality factor warning
message
Upper limit value for a power quality factor warning
message
sage
Lower limit value for an error message due to voltage
imbalance
Lower limit value for a warning message due to volt-
age imbalance
Upper limit value for a warning message due to volt-
age imbalance
Version: 1.5
Data type
Flags
Default
UINT8
RO
0x28 (40
REAL32
RW
47,000000
(4,700000e+001)
REAL32
RW
49,500000
(4,950000e+001)
REAL32
RW
50,500000
(5,050000e+001)
REAL32
RW
52,000000
(5,200000e+001)
REAL32
RW
EL3423, EL3443
0,000000
(0,000000e+000)
EL3453
-1,050000
(-1,050000e+000)
REAL32
RW
EL3423, EL3443
0,000000
(0,000000e+000)
EL3453
-1,000000
(-1,000000e+000)
REAL32
RW
EL3423, EL3443
0,006000
(6,000000e-003)
EL3453
1,000000
(1,000000e+000)
REAL32
RW
EL3423, EL3443
0,030000
(3,000000e-002)
EL3453
1,050000
(1,050000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
0,050000
(5,000000e-002)
REAL32
RW
0,800000
(8,000000e-001)
REAL32
RW
1,000000
(1,000000e+000)
REAL32
RW
1,000000
(1,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
0,000000
(0,000000e+000)
REAL32
RW
EL3423, EL3453
0,000000
(0,000000e+000)
EL3443
2,000000
(2,000000e+000)
)
dec
EL34xx

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents