Beckhoff EL34 Series Documentation page 164

3-phase energy and power measurement terminals
Table of Contents

Advertisement

Commissioning
Index F600 PMX Total Status
Index (hex) Name
F600:0
PMX Total Status
F600:01
System State
F600:02
Grid Direction
F600:03
Frequency Guard
Warning
F600:04
Frequency Guard Er-
ror
F600:05
Neutral Current Guard
Warning
F600:06
Neutral Current Guard
Error
F600:07
Active Power Guard
Warning
F600:08
Active Power Guard
Error
F600:09
Apparent Power
Guard Warning
F600:0A
Apparent Power
Guard Error
F600:0B
Power Quality Guard
Warning
F600:0C
Power Quality Guard
Error
F600:0F
TxPDO State
F600:10
TxPDO Toggle
F600:11
Power Quality Factor Analog value of the voltage quality between 1.0 and
Index F602 PMX Total Advanced
Index (hex) Name
F602:0
PMX Total Advanced Max. subindex
F602:01
Unbalance Guard
Warning
F602:02
Unbalance Guard Er-
ror
Index F603 PMX Total Active
Index (hex) Name
F603:0
PMX Total Active
F603:12
Active Energy
F603:13
Active Positive En-
ergy
F603:14
Active Negative En-
ergy
Index F605 PMX Total Apparent
Index (hex) Name
F605:0
PMX Total Apparent
F605:12
Apparent Energy
F605:13
Apparent Positive En-
ergy
F605:14
Apparent Negative
Energy
164
Meaning
Max. subindex
Overall system state (as a logical disjunction of volt-
age guard errors, phase sequence, overvoltage,
overcurrent and frequency guard errors)
Phase sequence L1 - L2 - L3 correctly detected (with
clockwise 3-phase mains)
A warning limit of the frequency monitor has been
breached.
An error limit of the frequency monitor has been
breached.
A warning limit of the neutral conductor current moni-
tor has been breached.
An error limit of the neutral conductor current monitor
has been breached.
A warning limit of the active power monitor has been
breached.
An error limit of the active power monitor has been
breached.
A warning limit of the apparent power monitor has
been breached.
An error limit of the apparent power monitor has been
breached.
A warning limit of the PQF monitor has been
breached.
An error limit of the PQF monitor has been breached. BOOLEAN
TRUE for general error
The TxPDO toggle is toggled by the slave when the
data of the associated TxPDO is updated.
0 (see basic function principles - Power Quality Fac-
tor)
Meaning
A warning limit of the unbalance monitor has been
breached.
An error limit of the unbalance monitor has been
breached.
Meaning
Max. subindex
Recorded active energy in mWh
Received active energy in mWh
Supplied active energy in mWh
Meaning
Max. subindex
Recorded apparent energy in mWh
Received apparent energy in mWh
Supplied apparent energy in mWh
Version: 1.5
Data type
Flags
Default
UINT8
RO
0x11 (17
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
REAL32
RO
0x00000000 (0
Data type
Flags
Default
UINT8
RO
0x02 (2
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
Data type
Flags
Default
UINT8
RO
0x14 (20
INT64
RO
INT64
RO
INT64
RO
Data type
Flags
Default
UINT8
RO
0x14 (20
INT64
RO
UINT64
RO
UINT64
RO
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
EL34xx

Hide quick links:

Advertisement

Table of Contents
loading