Beckhoff EL34 Series Documentation page 168

3-phase energy and power measurement terminals
Table of Contents

Advertisement

Commissioning
Index 90n3 PMX info data energy (for ch.1, n = 0; ch.2, n = 1; ch.3, n = 2)
Index (hex) Name
90n3:0
PMX info data energy
ch.1
90n3:11
Active Energy
90n3:12
Positive Active En-
ergy
90n3:13
Negative Active En-
ergy
90n3:14
Apparent Energy
90n3:15
Positive Apparent En-
ergy
90n3:16
Negative Apparent
Energy
90n3:17
Reactive Energy
90n3:18
Positive Reactive En-
ergy
90n3:19
Negative Reactive
Energy
Index A0n0 PMX Diag data (for ch.1, n = 0; ch.2, n = 1; ch.3, n = 2)
Index (hex) Name
A0n0:0
PMX diag data ch.1
A0n0:11
Saturation Time Volt-
age
A0n0:12
Saturation Time Cur-
rent
Index F081 Download revision
Index (hex) Name
F081:0
Download revision
F010:01
Revision number
Index F80F PM Vendor data
Index (hex) Name
F80F:0
PMX Vendor data
F80F:11
Type
Index F902 PMX Total Info data Power
Index (hex) Name
F902:0
PMX Total Info data
Power
F902:11
Active Power Avg
F902:12
Active Power Min
F902:13
Active Power Max
F902:14
Apparent Power Avg
F902:15
Apparent Power Min
F902:16
Apparent Power Max Maximum total apparent power in the last interval in
F902:17
Reactive Power Avg
F902:18
Reactive Power Min
F902:19
Reactive Power Max
168
Meaning
Max. subindex
Recorded active phase energy in mWh
Received active phase energy in mWh
Supplied active phase energy in mWh
Recorded apparent phase energy in mWh
Received apparent phase energy in mWh
Supplied apparent phase energy in mWh
Recorded reactive phase energy in mWh
Received reactive phase energy in mWh
Supplied reactive phase energy in mWh
Meaning
Max. subindex
Time (in 0.1 ms) in which the terminal has measured
an overvoltage.
Time (in 0.1 ms) in which the terminal has measured
an overcurrent.
Meaning
Max. subindex
Configured revision of the terminal,
(see note)
Meaning
Max. subindex
Vendor-specific data
Meaning
Max subindex
Average total active power during the last interval in
W
Minimum total active power in the last interval in W
Maximum total active power in the last interval in W
Average total apparent power during the last interval
in VA
Minimum total apparent power in the last interval in
VA
VA
Average total reactive power average during the last
interval in var
Minimum total reactive power in the last interval in
var
Maximum total reactive power in the last interval in
var
Version: 1.5
Data type
Flags
Default
UINT8
RO
0x19 (25
INT64
RO
UINT64
RO
UINT64
RO
INT64
RO
UINT64
RO
UINT64
RO
INT64
RO
UINT64
RO
UINT64
RO
Data type
Flags
Default
UINT8
RO
0x12 (18
UINT32
RO
0x00000000 (0
UINT32
RO
0x00000000 (0
Data type
Flags
Default
UINT8
RO
0x01 (1
UINT32
RW
0x00000000 (0
Data type
Flags
Default
UINT8
RO
0x11 (17
UINT32
RW
0x00000000 (0
Data type
Flags
Default
UINT8
RO
0x19 (25
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
EL34xx

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents