Beckhoff EL34 Series Documentation page 226

3-phase energy and power measurement terminals
Table of Contents

Advertisement

Commissioning
Index 90n3 PMX info data energy (for ch.1, n = 0; ch.2, n = 1; ch.3, n = 2)
Index (hex) Name
90n3:0
PMX info data energy
ch.1
90n3:11
Active Energy
90n3:12
Positive Active En-
ergy
90n3:13
Negative Active En-
ergy
90n3:14
Apparent Energy
90n3:15
Positive Apparent En-
ergy
90n3:16
Negative Apparent
Energy
90n3:17
Reactive Energy
90n3:18
Positive Reactive En-
ergy
90n3:19
Negative Reactive
Energy
Index 90n4 PMX Harmonic Voltage (for ch.1, n = 0; ch.2, n = 1; ch.3, n = 2)
Index (hex) Name
90n4:0
PMX Harmonic Volt-
age Ch.1
90n4:01
Harmonic 0
90n4:02
Harmonic 1
90n4:03
Harmonic 2
90n4:04
Harmonic 3
...
...
90n4:40
Harmonic 63
Index 90n5 PMX Harmonic Current (for ch.1, n = 0; ch.2, n = 1; ch.3, n = 2)
Index (hex) Name
90n5:0
PMX Harmonic Volt-
age Ch.1
90n5:01
Harmonic 0
90n5:02
Harmonic 1
90n5:03
Harmonic 2
90n5:04
Harmonic 3
...
...
90n5:40
Harmonic 63
Index 90n6 PMX Info data Fundamental (for ch.1, n = 0; ch.2, n = 1; ch.3, n = 2)
Index (hex) Name
90n6:0
PMX Info data Funda-
mental Ch.1
90n6:10
Voltage Fundamental
RMS
90n6:11
Voltage Fundamental
Frequency
90n6:12
Current Fundamental
RMS
90n6:13
Current Fundamental
Frequency
226
Meaning
Max. subindex
Recorded active phase energy in mWh
Received active phase energy in mWh
Supplied active phase energy in mWh
Recorded apparent phase energy in mWh
Received apparent phase energy in mWh
Supplied apparent phase energy in mWh
Recorded reactive phase energy in mWh
Received reactive phase energy in mWh
Supplied reactive phase energy in mWh
Meaning
Max. subindex
DC component of the oscillation in % of the funda-
mental wave
Fundamental wave
2nd harmonic in % of the fundamental wave
3rd harmonic in % of the fundamental wave
...
63rd harmonic in % of the fundamental wave
Meaning
Max. subindex
DC component of the oscillation in % of the funda-
mental wave
Fundamental wave
2nd harmonic in % of the fundamental wave
3rd harmonic in % of the fundamental wave
...
63rd harmonic in % of the fundamental wave
Meaning
Max. subindex
Effective voltage of the fundamental wave from the
harmonic calculation
Frequency of the fundamental voltage wave from the
harmonic calculation
Effective current of the fundamental wave from the
harmonic calculation
Frequency of the fundamental current wave from the
harmonic calculation
Version: 1.5
Data type
Flags
Default
UINT8
RO
0x19 (25
INT64
RO
UINT64
RO
UINT64
RO
INT64
RO
UINT64
RO
UINT64
RO
INT64
RO
UINT64
RO
UINT64
RO
Data type
Flags
Default
UINT8
RO
0x40 (64
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
...
...
...
REAL32
RO
0x00000000 (0
Data type
Flags
Default
UINT8
RO
0x2A (42
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
REAL32
RO
0x00000000 (0
...
...
...
REAL32
RO
0x00000000 (0
Data type
Flags
Default
UINT8
RO
0x13 (19
REAL32
RO
0.000000
(0.000000e+000)
REAL32
RO
0.000000
(0.000000e+000)
REAL32
RO
0.000000
(0.000000e+000)
REAL32
RO
0.000000
(0.000000e+000)
)
dec
)
dez
)
dez
)
dez
)
dez
)
dez
)
dez
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
EL34xx

Hide quick links:

Advertisement

Table of Contents
loading