Beckhoff EL34 Series Documentation page 250

3-phase energy and power measurement terminals
Table of Contents

Advertisement

Commissioning
6.7.5.4
Input data
Index 60n0 PMX status (n = 0, 1, 2)
Index (hex) Name
60n0:0
PMX Status
60n0:01
Voltage Sign Bit
60n0:02
Overvoltage
60n0:03
Overcurrent
60n0:04
Inaccurate Voltage
60n0:05
Inaccurate Current
60n0:06
Voltage Guard Warn-
ing
60n0:07
Voltage Guard Error
6000:10
TxPDO Toggle
Index 60n1*** PMX Basic (n = 0, 1, 2)
Index (hex) Name
60n1:0
PMX Basic
60n1:11
Voltage
***) only for EL3483-0060
250
Meaning
Max. subindex
Indicates the sign of the current sine wave voltage:
1 = U > 0V
0 = U < 0V
Maximum measurable voltage is exceeded.
Maximum measurable current is exceeded.
The measured voltage value is smaller than the value
entered in CoE object "F800:15 Inaccurate Threshold
Voltage".
The measured current value is smaller than the value
entered in CoE object "F800:16 Inaccurate Threshold
Current".
A warning limit of the voltage monitor has been
breached.
An error limit of the voltage monitor has been
breached.
The TxPDO toggle is toggled by the slave when the
data of the associated TxPDO is updated.
Meaning
 Max. Subindex
 RMS value of the voltage in V
Version: 1.5
Data type
Flags
Default
UINT8
RO
0x10 (16
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
BOOLEAN
RO
0x00 (0
Data type
Flags
Default
UINT8
RO
0x11 (17
REAL32
RO
0x00000000 (0
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec
)
dec