Menu J : SATURATE CUR
Important
Adjustment point setting condition
In the case that point is out of setting limit.
(Ex)
1-2: RERANGE
LRV
100.01%
digital indicator provided, if the range is changed,
indicator display might not match. So, setting is re-
quired again in response to the display in the digital
indicator (G:XMTR DISPLAY).
alog indicator provided, if the range is changed, the
scale for indicator might not ensure exact reading.
• When CHNG is pressed at display
lowing is displayed.
1-1: RERANGE
Set Linearize
MENU N° H:LINEARIZE is set in EFFECTIVE.
In this case, press the CL key and set in INVALID on
the panel of N° H:LINEARIZE.
88
CL
CL
URV
I-2:
RERANGE
URV 100.00%
< ENT > < CL >
CL
ENT
I-3:
RERANGE
CHANGE
URV
%
CHNG OK? < ENT/CL >
4
ENT
I-5: RERANGE
LRV
kPa
URV
kPa
< CL >
5
CL
or
, the fol-
Menu I : Adjustment by LRV/URV range
The Rerange functionality can be used when zero ad-
justment (suppression or elevation) is necessary (for
example : Level measurement).
Functions of RERANGE can be made with FXW Ver-
sion 6.0 or upward.
When the lower range value (LRV) and upper range
value (URV) need to be adjusted again during mea-
surement of tank level, the measurement levels can
be changed at the same time by setting the LRV with
rerange.
6
LRV Rerange
Apply an input pressure required for rerange of LRV at
7
display of
and press ENT twice.
In this way, the rerange of LRV is completed, then the
new measurement range LRV and URV, which con-
8
forms to the actual input pressure, is displayed.
URV Rerange
Apply an input pressure required for rerange of URV at
display of
and press ENT twice. The rerange of URV
is completed, then the new measurement range LRV
and URV corresponding to the actual input pressure is
displayed.
Note) The unit of LRV/URV at
in the unit selected by Menu N° 4:UNIT.
CAUTION
This rerange function adjusts imput and output by
range change.
Upon implementation of rerange, the measure-
ment range changes as follows :
-
If RERANGE
Measurement range (LRV and URV) changes.
However, span remains unchanged.
If RERANGE
Only URV (spam) of measurment range
changes. Zero POint (LRV) remains the same.
and
are displayed
LRV is implemented :
URV is implemented :
TN5FCXA2V5h-E