G
OUT
B:
OUTPUT ADJ
< INC > < CHANGE >
CHNG
INC
B-1: OUTPUT SET
0mA
< LRV/URV/ENT/CL >
1
LRV
URV ENT
CL
B-1: OUTPUT SET
B-1: OUTPUT SET
4.000mA
CHANGE OK? < ENT/CL >
CHANGE OK? < ENT/CL >
2
7
ENT
CL
(4 , 20mA)
B-2:
OUTPUT MODE
XX.XXXmA
CURRENT CONST.
< CALB > < CHNG > < CL >
3
CL
CALB
CHNG
B-3: OUTPUT CALIB
XX.XXXmA CONST.
0mA (EXT.mA)
< ENT > < CL >
4
CL
ENT
B-3:
OUTPUT CALIB
XX.XXXmA CONST.
YY.YYYmA (EXT.mA)
CHANGE OK? < ENT/CL >
5
CL
ENT
B-4:
OUTPUT
XX.XXXmA CONST.
YY.YYYmA (EXT.mA)
CALIBRATING
6
Calibration
impossible
B-4:
OUTPUT
XX.XXXmA CONST.
YY.YYYmA (EXT.mA)
NOT CAL1B. < CL >
10
CL
C:
DATA
After setting and calibrating the constant current output, be sure to reset the HHC
display to cancel with the inital display of menu B.
Important
It should be noted that if HHC is removed from the transmitter loop or the HHC power
is turned OFF when the constant current output has been set, the transmitter output
is retained at the constant current output.
80
(Input of XX.XXXmA at
1
B-1: OUTPUT SET
20.000mA
XX.XXXmA
CHANGE OK? < ENT/CL >
CL
CL
ENT
8
ENT
(OTHERS)
< OTHERS >
B-2:
OUTPUT MODE
XX.XXXmA
CURRENT CONST.
< CHANGE > < CL >
9
CL
CHNG
appears when the
10
adjustable range is
exceeded.
Menu B : Calibration of output circuit D/A
The transmitter has a numerical electronic. The
cell signals are processed by a microprocessor
and sent to a digital/analog D/A converter to con-
vert the signal in 4-20 mA.
This menu allows to calibrate the D/A converter. It
is necessary to connect a milliamperemeter (ac-
curacy +- 1micro A) to chack the output signal.
This menu allows too to check, with a 4-20 mA
)
signal, the measuring loop.
The output circuit (D/A) should be calibrated by
the following procedure when necessary.
Make transmitter connection according to "Cali-
bration" in appendix A2, and calibrate the output
circuit using the following procedure.
, the display
calibration will appear on the screen.
During this phase, a 4mA constant current is
generated.
- Press "CALB" for the calibration
- Press "CHNG" or "CL" to cancel
for 20mA current output and its calibration will
appear on the screen.
ated.
- Press "CALB" for the calibration
- Press "CHNG" or "CL" to cancel
Under display
to generat a constant current.
- Press "CHANGE" or "CL" to cancel.
Under display
by digital voltmeter.
Under display
The transmitter will calculate automatically the
gap between the theoritical and the measured
values. It will rectify in the D/A converter.
for 4mA current output and its
, input a desired value within a
, input digital values measured
, the output circuit is calibrated
B:
OUTPUT ADJ
<INC> <CHANGE>
TN5FCXA2V5h-E
-