6.2.2 Switching menus

Setting mode with the
Press the
key for a few seconds to switch the normal mode to the setting mode.
Press the
key for a few seconds to switch the setting mode to the normal mode.
After selecting an item with the
Normal mode
(A measured value is displayed.)
Press the
Setting mode
Item name selection screen
You can move to a next
upper item with the
key.
You can move to a next
lower item with the
key.
1. TAG
2. TYPE
3-1. SERIAL N
3-2. VER
4. UNIT
5. URL
6-1. LRV
6-2. URV
7. DAMP
8-1. OUT Md
8-2. CUT Pt
8-3. CUT Md
9-1. BURNOT
9-2. OVER
9-3. UNDER
A-1. ZERO
A-2. SPAN
B-1. 4mAAdj
B-2. 20mAAdj
B-3. FIXcur
D-1. AMPTMP
D-2. ALMCHK
F. LOCK
G-1. LDV
G-2. UDV
G-3. dP
G-4. LcdUnit
G-5. LcdOpt
I-1. LRVAdj
I-2. URVAdj
J-1. SAT LO
J-2. SAT HI
J-3. SPEC
K. GUARD
L-1. HisZERO
L-2. HisSPAN
L-3. HisCLEAR
L-4. HisAMP
L-5. HisCELL
TN5FCXA2V5h-E
button to select and display the differents menus.
/
key for two seconds or more.
key
1. Display and setting of TAG No.
2. Display and setting of type
3-1. Display of serial No.
3-2. Display of transmitter software version
4. Display and change of engineering unit
5. Display of maximum measuring range
6-1. Change of LRV (lower range value of measuring range = 0% point)
6-2. Change of URV (upper range value of measuring range = 100% point)
7. Change of damping time constant
8-1. Change of output mode
8-2. Setting of low flow rate cut point
8-3. Setting of low flow rate cut mode
9-1. Change of burnout direction
9-2. Chang of output value when burnout direction = OVERSCALE
9-3. Chang of output value when burnout direction = UNDERSCALE
A-1. Zero calibration
A-2. Span calibration
B-1. 4 mA calibration
B-2. 20 mA calibration
B-3. Constant current output
D-1. Display of internal temperature of transmitter
D-2. Display of self-diagnosis.
F. Locking and unlocking of the adjusting screw and the adjustment function in the setting mode
G-1. LDV (Lower Display Value) setting
G-2. UDV (Upper Display Value) setting
G-3. DP (Digit Number Under Decimal Point) setting
G-4. LcdUnit (LCD Unit Code) setting
G-5. LcdOpt (LCD Option) setting
I-1. Zero adjustment by range (LRV) change
I-2. Span adjustment by range (URV) change
J-1. Change of saturation current value (lower limit)
J-2. Change of saturation current value (upper limit)
J-3. Selection (nomal specification/expanded specification) of specifications of burnout & saturation current
K. Setting and cancellation of set value protection (write protect)
L-1. Display of zero calibration data for users
L-2. Display of span calibration data for users
L-3. Clearing of zero/span calibration data
L-4. Display of min/max of amplifier temperature history information
L-5. Display of min/max of cell temperature history information
keys, press the ) key to acess to the menu selected.
Setting mode
Display and setting of each item
43