7.4
Adjustment
After completion of the assembly work mentioned above, use the following procedures for
adjustment and setting. Adjustment should be performed using the HHC.
(1) After replacement of electronics unit (including replacement of internal parts)
Display symbol
No.
Item
rator unit with
1
TAG No.
1: TAG
2
Model code
2: TYPE
3-1: SERIAL No.
3
Serial No.
3-2: VER
4
Engineering unit
4: UNIT
5
Range limit
5: URL
6-1: LRV
6
Measuring range
6-2: URV
7
Damping
7: DAMP
8-1: OUT Md
8
Output mode
8-2: CUT Pt
8-3: CUT Md
9-1: BURNOUT
9
Burnout direction
9-2: OVER
9-3: UNDER
Zero/span
A-1: ZERO
10
calibration
A-2: SPAN
b-1: 4mAAdj
Calibration output
11
b-2: 20mAAdj
circuit
b-3: FIXcur
M e a s u r e m e n t
12
(Normal mode)
data
d1: AMPTMP
13
Self-diagnosis
d2: ALMCHK
14
Printer function
Lock of adjust-
15
F: LOCK
ment functions
G-1: LDV
G-2: UDV
Indication of
16
G-3: DP
digital indicator
G-4: LcdUnit
G-5: LcdOpt
Programmable
17
linearization
function
I n p u t - o u t p u t
I-1: LRVAdj
18
range adjustment
I-2: URVAdj
J-1: SAT LO
Change of
19
J-2: SAT HI
saturation current
J-3: SPEC
Protective func-
20
K: GUARD
tion of set value
L-1: His ZERO
L-2: His SPAN
History informa-
21
L-3: His CLEAR
tion
L-4: His AMP
L-5: His CELL
(2) After replacement of detecting unit (including replacement of internal parts)
Zero/span
A-1: ZERO
1
calibration
A-2: SPAN
TN5FCXA2V5h-E
-
(Relevant
page)
LCD display
(P44)
(P45)
(P46)
(P47)
(P47)
(P48)
(P50)
(P51)
(P53)
(P55)
(P57)
(P58)
-
(P59)
(P60)
-
(P63)
(P65)
(P67)
(P68)
(P55)
Display symbol of
(Relevant
HCC
page)
1: TAG No.
(P73)
2: TYPE
(P73)
3: SERIAL No.
(P74)
4: UNIT
(P74)
5: RANGE LIMIT
(P75)
6: RANGE
(P75)
7: DAMPING
(P76)
8: OUTPUT MODE
(P77)
9: BURNOUT
(P78)
A: CALIBRATE
(P879)
B: OUTPUT ADJ
(P80)
C:DATA
(P81)
D: SELF CHECK
(P81)
E: PRINT
(P82)
F: XMTR EXT.SW
(P82)
G: XMTR DISPLAY
(P83)
H: LINEARIZE
(P86)
I: RERANGE
(P88)
J: SATURE CUR
(P89)
K: WRITE PROTCT
(P90)
L: WRITE PROTCT
(P91)
A: CALIBRATE
(P79)
Contens of setting adjustment
Set the previous data before replacement of
amp unit.
Set the previous data before replacement of
amp unit.
Not necessary for operation
Set the previous data before replacement of
amp unit.
Not necessary for operation
Set the previous data before replacement of
amp unit.
Set the previous data before replacement of
amp unit.
Set the previous data before replacement of
amp unit.
Set the previous data before replacement of
amp unit.
Implement span calibration after zero calibra-
tion.
Loop check & calibrate fixed output current
(4mA,20mA)
Check the measurement data.
Check, if it is necessary.
In case of HHC with printer option, print if it is
necessary.
Set the previous data before replacement of
amp unit
Set the previous data before replacement of
amp unit.
Set the previous data before replacement of
amp unit.
Adjust the input-output range (RERANGE) as
required.
Set the previous data before replacement of
amp unit.
Set the previous data before replacement of
amp unit.
Check data as necessary
Implement span calibration after zero calibration
101