5- Pressure measurement for gas
Place the transmitter above the process pipes to pre-
venting condensation in the impulse pipe and in the
measuring
6- Level measurement
For measurement, connect the highest liquid level of tank with the low pressure side of
transmitter, and the lowest liquid level of tank with the high pressure side of transmitter.
The reference column (connected to the high-
Level calculation formula
: Density
0
1
H
, H
:
1
2
h:
(2) Reference column empty
For an open tank, leave the low pressure side of transmitter open to atmosphere.
Level calculation formula
: Density
1
H
: Liquid level,
1
h : Liquid level change
18
H
2
0
1
H
2
1
0
1
Liquid level,
Liquid level change
1
h
1
1
Atmospheric
air inlet
Pressure tap
Condensate chamber
ρ
ρ
0
H
1
Manifold
Low
High
pressure
pressure
side
side
ρ
1
Atmospheric
ρ
air inlet
Manifold
Low
pressure
side
Manifold
Impulse pipe
Isolating valve
Process pipe
ρ
1
Max. liquid level
h
Min. liquid level
H
2
Max. liquid
level
h
Min. liquid
level
H
1
High
pressure
side
TN5FCXA2V5h-E