(Cancel the setting)
M
(Save the setting)
66
M
M
J-3 SPEC : Selection of the burnout & saturation cur-
• Press the
screen for selecting the burnout & saturation current
panded specification)" on the screen
and
keys.
Select "NoRMAL" for the normal setting.
Select "EXP" for the expanded setting.
* To change the saturation current value (upper limit,
Saturation
current value
(lower limit)
Saturation
current value
(upper limit)
The table below lists the output current value for
burnout (OVER, UNDER).
Burnout
3.2 to 3.8 mA
(UNDER)
Burnout
20.8 to 21.6 mA
(OVER)
The values in the table above can be set in increments
of 0.1 mA.
• Select whether the NoRMAL/EXP setting is saved on
the screen .
Press the
key to save the NoRMAL/EXP setting.
Press the
or
to the screen
key on the screen
to display the
).
Normal
3.8 mA
3.2 mA to 4.0 mA
Settable in increments of
0.1 mA
20.8 mA
20.0 mA to 21.6 mA
Settable in increments of
0.1 mA
-
cation
3.2 mA to saturation current
value (lower limit)
Saturation current value
(upper limit) to 21.6 mA
key to cancel the setting and return
.