Menu 4 : UNIT
INC
5: RANGE LIMIT
XXX
kPa
< INC >
INC
6:
RANGE
XXX . X
LRV
kPa
XXX . X
URV
kPa
< INC > < CHANGE >
1
INC
To menu 7 : DAMPING
The setting range of the transmitter is independant of the setting range of the indicator.
After changing the range in this menu, it is necessary to change the range in the LCD
Important
indicator (menu G).
Using an analog indicator and the transmitter range is changed, replacement of the analog
indicator is required.
TN5FCXA2V5h-E
CHNG
6-1:
RANGE CHANGE
XXX . X
LRV
kPa
XXX . X
URV
kPa
< LRV > < URV > < CL >
CL
LRV
CL
6-2:
RANGE CHANGE
XXX . X
LRV
kPa
XXX . X
URV
kPa
< LRV > < URV > < CL >
CL
URV
6-2:
RANGE CHANGE
XXX . X
LRV
kPa
XXX . X
URV
kPa
< LRV > < URV > < CL >
ENT
CL
6-2:
RANGE CHANGE
XXX . X
LRV
kPa
XXX . X
URV
kPa
CHNG OK? < ENT/CL >
ENT
6-3:
RANGE WRITE
XXX . X
LRV
kPa
XXX . X
URV
kPa
Menu 5 : Range Limit
Indicates the maximum measuring range of this
transmitter.
• After setting engineering unit, press <INC
to display RANGE LIMIT.
• By pressing the <INC
is displayed
Menu 6 : Range change (LRV, URV)
2
LRV: Lower range value (0% point - 4 mA)
URV: Upper range value (100% point - 20 mA)
Selectable setting range
3
Reverse
URV
4
Maximum measuring range
Note) If the set value of the LRV is outside the
range, an error also occurs (SetERROR) in the
URV setting, and vice versa.
5
The maximum setting range is ± 9999.
The URV may excedd the upper limit depending
on the change of the Unit. If that happens change
6
• When pressing <CHNG
changes to the LRV and URV selection screen.
• Press <LRV
the zero point range (display
• Press <URV
the span range (display
• Under displays
values. Press <ENT
Note : when pressing <+
or
, negative value is available
Note : if the set value of the LRV is outside
the range, an error ("setting error") also occurs
in the URV setting, and vice versa.
The maximum setting range is ±99999.
The URV may exceed the upper limit depending
on the change of the UNIT.
.
Output (mA)
20
action
Normal
Input
action
4
LRV LRV
URV
).
).
or
, input zero point or span
-
, display
.
75