Menu I : Rerange: adjustment by LRV/URV
change
(Specially for application to level measurement)
The input-output range adjustment enables you to
change automatically the measurement range by re-
adjusting the lower limit of the measurement (LRV) or
the upper limit of the measurement (URV).
I-1 LRV Adj : Zero adjustment by changing the
range (LRV) (LRV adjustment)
• Press the
key on the screen
adjustment mode.
The measured value and unit on the screen
"ZERO" light up.
• Apply the reference pressure for LRV (4mA) on the
screen
. After checking the measured value corre-
sponding to 4 mA, press the
• "ZERO" blinks on the screen
the screen
to perform a zero adjustment at the in-
put pressure.
Settable range:
• Select whether the LRV adjustment value setting is
saved on the screen
Press the
key to save the LRV adjustment value
setting and return to the screen
Press the
or
key to cancel the setting and return
to the screen
.
• Check that the zero adjustment (LRV) was performed
as intended on the screen
Press the
key to perform a zero adjustment again.
Press the
or
key to move to the next screen for
item name selection.
to select the LRV
key.
. Press the
key on
.
.
.
are
63